Single Phase Din Rail Split Type Prepaid Electricity Meter
a STE18-D operates with a 35 mm Din Rail mounting and pole mounting accessories, consists of two parts. A customer interface unit (CIU), and a metering and control unit (MCU). A CIU is a keypad based display to be installed within consumers homes wherever there is a plug point. MCU is the main meter, installed away from consumer’s home in a kiosk, meter box and pole-mounted enclosure.
MCU communicates with CIU via wireless communication such as Power Line Carrier (PLC), Radio Frequency (RF), LORA or 2-wires. This non-wired setup allows for easy inspection by utility and service providers at any time without visiting consumers’ houses and reduces the chance of fraud by tampering.
Electrical Parameters
Nominal Voltage | 230V |
Working Voltage Range | 70%~120%Un |
Nominal Frequency | 50-60Hz |
Basic Current (Ib) | 5A |
Maximum Current (Imax) | 80A |
Starting Current (Ist) | 20mA |
Active Energy Constant | 1000imp/kWh |
Measurement Accuracy | Class 1.0 |
Power Consumption in Voltage Circuit | <2W <8VA |
Power Consumption in Current Circuit | <1VA |
Operation Temperature Range | -25℃-70℃ |
Storage Temperature Range | -40℃-85℃ |
Electric Magnetic Compatibility
AC Insulation Strength | 4kV at 50Hz during 1min | |
Impulse voltage 1.2/50 us mains connections | 8kV | |
Electrostatic Discharges
|
Contact discharge | 8kV |
Air discharge | 16kV | |
Electromagnetic RF Field | 27MHz-500MHz | 10V/m |
100KHz-1GHz | 30V/m | |
Fast transient burst test | 4kV | |
Protection | Class II | |
Meter shell Water proof protection Rate | IP54 |
Basic Functions
✽ Meter Recharge By Inputting TOKEN
✽ Active energy measurement
✽ MD(maximum demand measurement)
✽ Auto scroll mode display
✽ Build-in relay control
✽ Event log
✽ Low Credit Alarm